Contaminants
|
Violation
(Yes/No)
|
Date
of
Sample
|
Level
Detected
(Maximum)
(Range)
|
Unit
Measure-
ment
|
MCLG
|
Regulatory
Limit
(MCL
or AL)
|
Likely
Source of Contaminant
|
|
Inorganic
Contaminants
|
Copper
|
No
|
July
/ August / September 2014 |
ND
- 0.3 0.1
(1) |
mg/L
|
1.3
|
AL
= 1.3
|
Corrosion
of household plumbing systems; Erosion of natural deposits
|
Lead
|
No
|
July / August /
September 2014
|
ND
- 1.7
1.0
(1) |
ug/L
|
1.3
|
AL
= 15
|
Corrosion
of household plumbing systems; Erosion of natural deposits
|
Barium
|
No
|
02/24/15
|
0.01
-0.03 |
mg/L
|
n/a
|
MCL = 20
|
Naturally
occurring
|
Ammonia
|
|
05/07/15
|
ND - 0.9 |
mg/L
|
n/a
|
NONE
|
Naturally
occurring
|
Sodium
|
No
|
04/20/15 |
18.0 - 47.0 |
mg/L
|
n/a
|
No
MCL(2)
|
Naturally
occurring
|
Iron |
No |
05/04/15 |
ND -
49 |
mg/L |
n/a
|
MCL
= 300 |
Naturally
occurring |
Zinc
|
No
|
02/26/15 |
ND
- 0.06 |
mg/L
|
n/a
|
MCL
= 5
|
Naturally
occurring
|
Nickel |
No |
02/26/15 |
ND -
5.6 |
ug/L |
n/a |
MCL
=
100 |
Naturally
occurring |
Magnesium
|
No
|
03/24/15 |
8.0
- 16.0 |
ug/L |
n/a
|
No
MCL
|
Naturally
occurring
|
Chloride
|
No
|
03/24/15 |
39.1
- 120.0 |
mg/L
|
n/a
|
MCL
= 250
|
Naturally
occurring
|
Calcium
|
No
|
03/24/15 |
15.0-
27.0 |
mg/L
|
n/a
|
No
MCL
|
Naturally
occurring
|
Nitrate
|
No
|
01/26/15 |
3.7-
6.4 |
mg/L
|
10
|
MCL
= 10
|
Runoff
from fertilizer and leaching from septic tanks and sewage
|
Selenium |
|
03/24/15 |
ND - 3.3 |
ug/L |
n/a |
MCL
= 50 |
Naturally
occurring |
Sulfate
|
No
|
04/20/15 |
20.4
- 44.1 |
mg/L |
n/a
|
MCL
= 250
|
Naturally
occurring
|
Perchlorate
|
No
|
12/10/15 |
ND
- 1.2 |
ug/L
|
n/a
|
AL
= 18 (3)
|
Fertilizer
|
Volatile
Organic Contaminants
|
Tetrachloroethene
|
No
|
09/16/15
|
ND
- 0.96
|
ug/L
|
0 |
MCL
= 5
|
Industrial/Commercial
Discharge
|
MTBE
|
No
|
12 /29/15
|
ND
- 0.63
|
ug/L
|
0 |
MCL
= 10
|
Gasoline
Additive
|
Total
Trihalomethanes
|
No
|
04/20/15
|
ND
- 14.6
|
ug/L
|
n/a
|
MCL = 80
|
Disinfection
By-Products
|
Synthetic
Organic Contaminants Including Pesticides and Herbicides
|
bis(2-Ethylhexyl)adipate
|
No
|
12/16/15
|
ND
- 0.67
|
ug/L
|
--
|
MCL = 400
|
Hydraulic Fuild
|
Radionuclides
|
Gross
Alpha |
No |
12/17/13 |
0.94
- 3.58 |
pCi/L |
n/a |
MCL
= 15 |
Naturally
occurring |
Radium
226 |
No |
12/17/13 |
0.09
- 1.84 |
pCi/L |
n/a |
MCL
= 5(4) |
Naturally
occurring |
Radium
228 |
No |
12/17/13 |
0.39
- 1.73 |
pCi/L |
n/a |
MCL = 5(4) |
Naturally
occurring |
Unregulated Contaminant
Monitoring Regulation (UCMR) Contaminants(5)
|
1.4
Dioxane |
No |
04/17/14 |
0.11
- 3.9 |
ug/L |
n/a |
No
MCL |
Naturally
occurring |
Chromium |
No |
0 9/02/14 |
ND
- 1.0 |
ug/L |
100 |
MCL
= 100 |
Naturally
deposits |
Hexavalent
Chromium |
No |
05/27/14 |
ND
- 1.1 |
ug/L |
n/a |
No
MCL |
Naturally
deposits |
Strontium |
No |
05/27/14 |
77.8
- 86.7 |
ug/L |
n/a |
No
MCL |
Naturally
occurring |
Chlorate |
No |
04/17/14 |
ND
- 140 |
ug/L |
n/a |
No
MCL |
Naturally
occurring |
Maximum
Contaminant Level (MCL)- The highest level of a contaminant that
is allowed in drinking water. MCLs
are set as close to the MCLGS as feasible.
Maximum
Contaminant Level Goal (MCLG)- The level of a contaminant in
drinking water below which there is no known or expected risk to health. MCLGs
allow for a margin of safety.
Action
Level (AL) – The concentration of a contaminant which, if
exceeded, triggers treatment or other requirements which a water system
much follow.
Milligrams
per liter (mg/l) – Corresponds to one part of liquid in one
million parts of liquid (parts per million – ppm).
Micrograms
per liter (ug/l) – Corresponds to
one part of liquid in one billion parts of liquid (parts per billion –
ppb).
Non-Detects(ND)
– Laboratory analysis indicates that the constituent is not present.
PCI/L
- Pico Curies per Liter is a
measure of radioactivity in water.
(1)
- During 2014 we collected and analyzed 30 samples for lead and copper.
The 90% percentile level is presented in the table. The action levels for
both lead and copper were not exceeded at any site tested.
(2)
- No MCL has been established for sodium. However, 20 mg/l is a
recommended guideline for people on high restricted sodium diets and 270
mg/l for those on moderate sodium diets.
(3)
- Perchlorate is an unregulated contaminant. However, the State Department
of Health has established an action level of 18 ug/L.
(4)
- MCL for radium 226 and 228 is a combined total radium = 5 pCi/L.
(5)
- UCMR3 - Unregulated Contaminant Monitoring Rule 3 is a Federal water
quality sampling program where water suppliers sample and test their
source water for one year. Results will be used by EPA to determine if the
contaminants need to be regulated in the future.