GARDEN CITY PARK WATER DISTRICT

2007 WATER QUALITY REPORT

TABLE OF DETECTED PARAMETERS

 
 

 

 

Contaminants

 

Violation

(Yes/No)

 

Date of

Sample

Level Detected

(Maximum)

(Range)

Unit

Measure-

ment

 

 

MCLG

 

Regulatory Limit

(MCL or AL)

 

 

Likely Source of  Contaminant

 

Inorganic Contaminants

Copper

No

June, July, Aug. 2005

ND - 0.1(1)

mg/l

1.3

AL =1.3

Corrosion of galvanized pipes; Erosion of natural deposits

Lead

No

June, July, Aug. 2005

ND - 1.14(1)

ug/l

0

AL =15

Corrosion of household plumbing systems; Erosion of natural deposits

Iron

No

9/12/2007

ND

ug/l

N

MCL = 300

Naturally occurring

Sodium

No

12/5/2007

16.4 - 32.4

mg/l

n/a

No MCL(2)

Naturally occurring

Magnesium

No

1/3/2007

8.5 - 15.5

mg/l

n/a

None

Naturally occurring

Chloride

No

12/5/2007

29.2 - 79.8

mg/l

n/a

MCL=250

Naturally occurring

Calcium

No

1/3/2007

15.8 - 24.4

mg/l

n/a

No MCL

Naturally occurring

Nitrate

No

12/3/2007

3.4 - 5.3

mg/l

10

MCL=10

Runoff from fertilizer and leaching from septic tanks and sewage

Sulfate

No

1/9/2007

5.9 - 39.8

mg/l

n/a

MCL=250

Naturally occurring

Perchlorate

No

5/17/2006

ND - 1.4

ug/l

n/a

None(3)

Fertilizer

   Radionuclides
Gross Alpha No

1/24/2007

ND - 3.2 pCi/L

n/a

MCL = 15 Naturally occurring
Radium 228 No

4/5/2007

ND-2.2 pCi/L None No MCL Naturally occurring

Synthetic Organic Contaminants Including Pesticides and Herbicides

None Detected

--

--

ND

--

--

--

--

Volatile Organic Contaminants

Tetrachloroethene

No

10/6/2007

ND - 4.2

ug/l

0

MCL=5

Industrial/Commercial Discharge

Trichloroethene

No

8/7/2007

ND - 02.6

ug/l

0

MCL=5

Industrial/Commercial Discharge

MTBE

No

5/1/2007

ND - 1.2

ug/l

0

MCL = 10

Gasoline Additive

Total Trihalomethanes

No

1/8/2007

ND - 2.5

ug/l

n/a

MCL = 80

Disinfection By-Product

 

DEFINITIONS

Maximum Contaminant Level MCL)- The highest level of a contaminant that is allowed in drining water. MCLs are set as close to the MCLGS as feasible.

Maximum Contaminant Level Goal (MCLG)- The level of a contaminant in drinking water below which there is no known or expected risk to health. MCLGs allow for a margin of safety.

Action Level (AL) – The concentration of a contaminant which, if exceeded, triggers treatment or other requirements which a water system much follow.

Milligrams per liter (mg/l) – Corresponds to one part of liquid in one million parts of liquid (parts per million – ppm).

Micrograms per liter (ug/l) – Corresponds to one part of liquid in one billion parts of liquid (parts per billion – ppb).

PCI/L Pico - Curies per Liter is a measure of radioactivity in water.

Non-Detects(ND) – Laboratory analysis indicates that the constituent is not present.

(1) - During 2005 we collected and analyzed 30 samples for lead and copper. The 90% percentile level is presented in the table. The action levels for both lead and copper were not exceeded at any site tested.

(2) - No MCL has been established for sodium. However, 20 mg/l is a recommended guideline for people on high restricted sodium diets and 270 mg/l for those on moderate sodium diets.

(3) - Perchlorate is not regulated by the USEPA. However, New York State has set an action level of 18.0 ppb.